We provide single, two or three phase units, with one or two secondary windings that can be dual class, i.e. 0.5/3P. The 3.6kV and 6.6kV units can be fully insulated for phase-to-phase operation.
Enclosure:
High voltage oil-filled tanks are available in the following finishes:
Ratios:
3.3kV, 6.6kV, 11kV, 22kV and 33kV with 36.67/63.5/110V Secondaries.
Burden:
Depends on the requirements but usually less than 100VA.
Class:
Metering and protection classes can be accommodated.
Insulation:
Uninhibited oil.
Connections:
Normally YNyn0 with optional delta secondary
Primary Terminations:
Tin-plated palm terminals on porcelain bushings.
Secondary Terminations:
Klippon SAK 6N terminals or fuses.
Testing:
Manufactured to IEC or AS standards. All transformers are tested in the TWS Energy Controls' high voltage test laboratory and supplied with test certificates to meet the requirements of the standards.
Enclosure:
Resin cast
Ratios:
3.3KV, 6.6KV, 11KV,22KV and 36KV with 36.67/63.5/110V secondaries
Burden:
Depends on class but up to 100VA/Phase
Class:
Metering and protection classes can be accommodated.
Testing:
Manufactured to IEC or AS standards. All transformers are tested in the TWS Energy Controls' high voltage test laboratory and supplied with test certificates to the requirements of the standards.